Hydrometer Registers

Reading a Hydrometer Register

Register Dials Pulse Reed Switch

Standard Register

Total Flow is calculated by adding the readings from the Totalizer and the three fractional dials. The three fractional dials measure quantities smaller than the totalizer reading and are continuously turning while calculating the flow.

Totalizer Reading

Rotates sequentially for each 1000 U.S.G. (U.S. Gallons) calculated Number displayed is multiplied by 1000 to reach total U.S.G.

Fractional Dial 1 (right dial) Each number (1-9) on the dial is multiplied by 100 to reach U.S.G. One complete revolution on this dial = 1000 U.S.G.

Fractional Dial 2 (lower center dial) Each number (1-9) on the dial is multiplied by 10 to reach U.S.G. One complete revolution on this dial = 100 U.S.G.

Fractional Dial 3 (left dial) Each number (1-9) on the dial is multiplied by 1 to reach U.S.G. One complete revolution on this dial = 10 U.S.G.

Hydrometer

Register Electrical Output

Netafim USA Hydrometers are equipped with electrical output devices which combine the high reliability of hermetically sealed, magnetically driven registers with electric transducer output options.

Applications
For automation and communicating with controllers and other devices Where more than just the traditional register is required

Features & Benefits
Equipped with electrical output devices Combines high reliability of hermetically sealed, magnetically driven registers with a wide variety of electric output options Magnetic registers can be easily changed to accommodate a variety of electrical outputs

Available Register Options

Netafim USA has three types of transducer outputs available which provide three levels of resolution:

  • Reed Switch (RS) Register - low frequency pulse output for functions related primarily to recording volume.
  • Photo Diode (PD) Register - standard frequency pulse output (open collector) for functions such as rate of flow and recording total volume.
  • Photo Diode (PDH) Register - high frequency pulse (open collector) for functions such as rate of flow and recording total volume.
Reed Switch (RS) Low Frequency Pulse Outputs

Reed Switch (RS) Register Specifications

  • Magnet activated.
  • Acts as a “dry contact”, uses very little electric power.
  • For “Volume” related functions such as data recorders or simple counters. (open collector) for functions such as rate of flow and recording total volume.

Electrical Specifications

  • Maximum Contact Current: 50 mA
  • Maximum Contact Voltage: 48 VDC
Reed Switch Outputs Circuit Diagram

Photo-Diode Electrical Specifications

POSITIVE powers the IR light (yellow wire)
Current Min: 15 mA to a maximum of 25 mA DC through a resistor

  • Maximum Voltage: 28 VDC

OUTPUT (clear wire)

  • Output – Open collector
  • (Max. Load – 2 mA)

GROUND (bare wire)

Photo-Diode (PD & PDH) Register

  • Sensor combines an IR light source and a light sensitive diode in one package.
  • Signals are created when the light beam created by the IR light is interrupted by a rotating element.
  • Requires a constant supply of DC power.
  • Recommended Resistor Values

    Photo Diode (PD) Standard Frequency Pulse Outputs

    Photo-Diode (PDH) High Frequency Pulse Outputs

    Photo Diode Circuit Diagram